Defintion of Subcooling
A sub-cooled liquid refrigerant is at a temperature below
(colder-than) the temperature at which the refrigerant would evaporate
("boil" or change from a liquid refrigerant to a gas - also called the
refrigerant saturation temperature).
Subcooling is measured in degrees of temperature (on any scale) and
can be defined as the difference in temperature degrees between the
liquid refrigerant's saturation temperature and the current or actual
liquid refrigerant temperature.
Higher subcooling temperatures of a liquid refrigerant mean a more
efficient HVACR system operation beause more heat is being removed per
unit volume (or unit weight) of refrigerant circulating in the system.
Thus some HVACR technicians measure subcooling to take a look at the
operating efficiency of the system and to compare it with the
manufacturer's specifications. Higher subcooling numbers mean that the
equipment will have to run less time to adequately cool the area being
refrigerated or air conditioned.
Lower or too-low subcooling temperatures risk accidental conversion
of liquid refrigerant to gas state within the piping system before it
reaches the refrigerant metering device (capillary tube or thermostatic
expansion valve (TEV)), reducing the efficiency of the system and
possibly interfering with the proper operation of the TEV. - adapted from Emerson Climate Technologies (2005)
Danfoss (2005) TEV fitters notes provides details about subcooling on HVACR equipment, from which we quote this excerpt:
Subcooling is defined as the difference between condensing pressure/temperature and liquid temperature at the expansion valve inlet. Subcooling is measured in Kelvin (K) or °C.
Subcooling of the refrigerant is necessary to avoid vapour bubbles in the refrigerant ahead of the expansion valve. Vapour bubbles in the refrigerant reduce capacity in the expansion valve and thereby reduce liquid supply to the evaporator. ubcooling of 4-5K is adequate in most cases. - Danfoss (2005)
Subcooling temperatures are measured on the refrigerant line just ahead of (supplying refrigerant into) the TEV.
External Pressure Equalization type Thermostatic Expansion Valves
For completeness we include this helpful note also from Danfoss,
describing the requirement for external pressure equalization type
expansion valves:
Expansion valves with external pressure equali- zation must always be used if liquid distributors are installed. Typically, the use of distributors gives a pressure drop of 1 bar across distributor and distribution tubes.Expansion valves with external pressure equalization should always be used in refrigeration systems with small compact evaporators, e.g. plate heat exchangers, where normally the pressure drop will be greater than pressure corresponding to 2K. - Danfoss (2005)
ليست هناك تعليقات:
إرسال تعليق